The selection of transformer oil filtration accuracy requires a comprehensive consideration of voltage level, oil contamination level, and the equipment manufacturer's requirements. The following is a specific selection guide:
1. Voltage Level Determines Baseline Accuracy
- ≤35kV: 5-10 microns (routine maintenance, removal of mechanical impurities).
- 110-220kV: 3-5 microns (control of particulate matter, avoidance of partial discharge).
- ≥500kV (UHV): 1-3 microns (requires vacuum dehydration, particle size ≤ NAS Class 7).
2. Dynamic Adjustment of Contamination Level
- Light contamination (ISO 18/16/13 particle count): 5-micron filter element + vacuum dehydration.
- Severe contamination (ISO 21/19/16 or emulsification): First, coarse filtration (20 microns) to remove large particles, then fine filtration to 1 micron.
| Standard Reference | Cleanliness Requirements | Corresponding Filtration Accuracy |
|-----------------------|----------------------------------------|---------------------------------------|
| IEC 60422 | Particle Count ≤5000/mL (≥110kV) | ≤3 microns |
| GB/T 14542 | Moisture ≤15ppm (UHV) | Requires Vacuum + 1 micron |
| ASTM D6786 | NAS 1638 Level 6 (UHV) | ≤1 micron |
1. New Oil Injection
- Accuracy: 3-5 microns (removes impurities during transportation/storage).
- Equipment: Plate and Frame Oil Filter + Molecular Sieve Adsorption (controls moisture ≤20ppm).
2. Operating Oil Maintenance
- Routine Filtration: 5 microns (monthly inspection, combined with particle counting).
- Post-overhaul filtration: 1 micron + vacuum treatment (dissipation loss ≤ 0.5%).
3. Fault recovery
- Moisture/minor deterioration: 3 micron + vacuum oil filter (moisture ≤ 10 ppm).
- Carbonization/heavy contamination: 1 micron + clay adsorption (acid value ≤ 0.1 mg KOH/g).
- Post-Filtration Testing:
- Particle Size (ISO 4406)
- Moisture (GB/T 7600)
- Dielectric Loss (IEC 60247)
| Voltage Level | Filter Element Precision | Required Features | Target Specifications |
|----------------|---------------------------|----------------------------------------|----------------------------------------------------------|
| 10kV | 10 micron | Plate and Frame Filter | Particle Count ≤ ISO 20/18/15 |
| 220kV | 3 micron | Vacuum + Glass Fiber Filter | Moisture ≤ 15ppm, NAS Level 8 |
| 1000kV | 1 micron | Vacuum + Electrostatic Purification | Dielectric Loss ≤ 0.3%, Particle Count ≤ NAS Level 6 |
Transformer oil filtration accuracy should be tailored to the specific application, based on voltage levels and contamination data. A phased, progressive filtration approach is preferred, with regular oil filtration tests verifying effectiveness.
Root Causes of Loss of Control in Vacuum Oil Purification Systems
How Industrial Oil Filters Remove Water and Impurities: A Comparison of Technical Principles
How to Choose the Right Industrial Oil Purifier: A Comprehensive Buyer’s Guide
How to Choose the Right Oil Purifier for Different Oil Types?
Double-Stage Vacuum Pumping: The Complete Guide to Transformer Maintenance