Transformer waste oil filtration and regeneration methods
Transformer waste oil filtration and regeneration are important to power equipment maintenance. The following is a systematic treatment method:
1. Sedimentation separation method
- Natural sedimentation: let stand for more than 72 hours, and use gravity to separate water and impurities
- Heating sedimentation: heat to 60-70℃ to accelerate sedimentation (pay attention to fire prevention)
- Centrifugal sedimentation: Use a centrifuge to quickly separate large particle impurities
2. Coarse filtration treatment
- Metal filter filtration: 100-200 mesh stainless steel filter to remove visible particles
- Filter paper filtration: Use special filter paper for preliminary purification
- Bag filtration: multi-layer fiber bag filter for large particle pollutants
1. Vacuum dehydration and degassing method
- Working principle: treatment at 50-70℃, vacuum degree -0.095~-0.099MPa
- Treatment effect: water content can be reduced to below 10 ppm
- Equipment type:
- Single-stage vacuum oil filter
Double-stage high vacuum oil filter
2. Precision filtration technology
- Filter element type:
- Cellulose filter element (precision 5-10μm)
- Glass fiber filter element (precision 1-3μm)
- Stainless steel sintered filter element (cleanable and reusable)
- Multi-stage filtration system: connect filter elements of different precisions in series to achieve gradient purification
3. Adsorption regeneration method
- Commonly used adsorbents:
- Activated clay (dosage 3-8%)
- Silica gel (particle size 2-5mm)
- Activated alumina
- Molecular sieve
- Treatment process:
- Contact method: direct mixing and stirring of oil and adsorbent
- Percolation method: oil passes through the adsorbent bed
1. Electrostatic oil purification technology
- Applicable objects: fine particles (0.1-1μm) and colloidal substances
- Electric field strength: 10- 20kV/cm
- Treatment effect: More than 99% of submicron particles can be removed
2. Centrifugal separation technology
- High-speed centrifuge: speed 6000- 15000 rpm
- Processing capacity: suitable for waste oil with high water content (>1000ppm)
- Advantages: no consumption of filter material, suitable for large-scale processing
3. Membrane separation technology
- Ultrafiltration membrane: molecular weight cutoff 1000-300000 Dalton
- Nanofiltration membrane: removes soluble impurities
- Reverse osmosis: deep dehydration
Recycled oil should meet the following key indicators:
- Breakdown voltage: ≥60kV/2.5mm (new oil standard)
- Water content: ≤15ppm
- Acid value: ≤0.03mgKOH/g
- Dielectric loss factor (90℃): ≤0.005
- Interfacial tension: ≥35mN/m
1. Safety protection:
- Firefighting equipment should be equipped at the processing site
- Operators should wear protective equipment
- Do a good job of grounding during electrostatic treatment
2. Environmental protection requirements:
- Waste adsorbents should be treated as hazardous waste
- Pickling wastewater should be discharged after neutralization
- Waste gas should be collected and treated
3. Economic considerations:
- Treatment costs should not exceed 60% of the price of new oil
- Severely aged oil (acid value>0.5mgKOH/g) is not recommended to be regenerated
4. Equipment maintenance:
- Regularly replace filter elements
- Vacuum pump oil is replaced every 500 hours
- Regularly descale the heating system
By reasonably selecting the treatment process, about 80% of transformer waste oil can be restored its performance and realize resource recycling. For transformer oil of 500kV and above, it is recommended to entrust a professional oil service company to handle it.