The selection of transformer oil filtration accuracy requires a comprehensive consideration of voltage level, oil contamination level, and the equipment manufacturer's requirements. The following is a specific selection guide:
1. Voltage Level Determines Baseline Accuracy
- ≤35kV: 5-10 microns (routine maintenance, removal of mechanical impurities).
- 110-220kV: 3-5 microns (control of particulate matter, avoidance of partial discharge).
- ≥500kV (UHV): 1-3 microns (requires vacuum dehydration, particle size ≤ NAS Class 7).
2. Dynamic Adjustment of Contamination Level
- Light contamination (ISO 18/16/13 particle count): 5-micron filter element + vacuum dehydration.
- Severe contamination (ISO 21/19/16 or emulsification): First, coarse filtration (20 microns) to remove large particles, then fine filtration to 1 micron.
| Standard Reference | Cleanliness Requirements | Corresponding Filtration Accuracy |
|-----------------------|----------------------------------------|---------------------------------------|
| IEC 60422 | Particle Count ≤5000/mL (≥110kV) | ≤3 microns |
| GB/T 14542 | Moisture ≤15ppm (UHV) | Requires Vacuum + 1 micron |
| ASTM D6786 | NAS 1638 Level 6 (UHV) | ≤1 micron |
1. New Oil Injection
- Accuracy: 3-5 microns (removes impurities during transportation/storage).
- Equipment: Plate and Frame Oil Filter + Molecular Sieve Adsorption (controls moisture ≤20ppm).
2. Operating Oil Maintenance
- Routine Filtration: 5 microns (monthly inspection, combined with particle counting).
- Post-overhaul filtration: 1 micron + vacuum treatment (dissipation loss ≤ 0.5%).
3. Fault recovery
- Moisture/minor deterioration: 3 micron + vacuum oil filter (moisture ≤ 10 ppm).
- Carbonization/heavy contamination: 1 micron + clay adsorption (acid value ≤ 0.1 mg KOH/g).
- Post-Filtration Testing:
- Particle Size (ISO 4406)
- Moisture (GB/T 7600)
- Dielectric Loss (IEC 60247)
| Voltage Level | Filter Element Precision | Required Features | Target Specifications |
|----------------|---------------------------|----------------------------------------|----------------------------------------------------------|
| 10kV | 10 micron | Plate and Frame Filter | Particle Count ≤ ISO 20/18/15 |
| 220kV | 3 micron | Vacuum + Glass Fiber Filter | Moisture ≤ 15ppm, NAS Level 8 |
| 1000kV | 1 micron | Vacuum + Electrostatic Purification | Dielectric Loss ≤ 0.3%, Particle Count ≤ NAS Level 6 |
Transformer oil filtration accuracy should be tailored to the specific application, based on voltage levels and contamination data. A phased, progressive filtration approach is preferred, with regular oil filtration tests verifying effectiveness.