The purification temperature of transformer oil (insulating oil) needs to balance dehydration/degassing efficiency and oil stability. The specific requirements are as follows:
- Optimum temperature: 50~65℃
- Vacuum oil filter (main equipment): usually set at 55~65℃ (heater outlet oil temperature).
- Pressure oil filter: 40~60℃ (avoid high temperature damage to filter material).
Temperature selection basis
Temperature range:<50℃
Impact:Water evaporates slowly, vacuum degassing efficiency is low, especially the removal effect of dissolved water is poor.
Temperature range:| 50~65℃
Impact:Optimum balance point: water evaporates quickly (up to more than 90%), gas escapes, and oil oxidation is controllable.
Temperature range:>70℃
Impact:Risk: accelerate oil oxidation (increase in acid value), damage antioxidant additives (such as T501).
- High water content oil (such as water content>50ppm): can be temporarily heated to 65~70℃, but the processing time needs to be shortened (≤4 hours).
- High viscosity oil (such as old oil in cold areas): can be appropriately raised to 60~70℃ to reduce viscosity, but the acid value needs to be monitored.
- Nano oil filtration technology: low temperature operation (30~50℃) to avoid high temperature damage to the nano filter membrane.
- Flash point limit: the purification temperature must be at least 20℃ lower than the oil flash point (such as the flash point of typical transformer oil ≥140℃, the temperature should be ≤120℃).
- Vacuum coordination: high temperature needs to be combined with high vacuum (such as ≤0.5kPa) to avoid local oil overheating.
- Hot oil circulation: when the transformer body is heated, the difference between the winding temperature and the oil temperature must be ≤10℃ (to prevent local overheating).
- IEC 60422:
- Oil index after purification: moisture ≤10ppm (transformer above 330kV), ≤15ppm (below 110kV);
- Withstand voltage ≥60kV (2.5mm gap).
- GB/T 7595: requires oil temperature ≤65℃ during purification, and acid value change ≤0.01mg KOH/g.
1. Pretreatment test: Determine the moisture, acid value, and dielectric loss (tanδ) in the oil to determine the heating intensity.
2. Step heating: First, circulate at low temperature (40℃) to remove free water, and then raise to 60℃ to remove dissolved water.
3. Real-time monitoring:
- Online moisture sensor (such as PPM detector);
- The temperature difference between the oil temperature in the vacuum tank and the outlet temperature of the heater must be ≤5℃ (to avoid local overheating).
- Oil aging: Temperature > 70℃ for 2 hours may lead to an increase in oxidation products (such as furfural).
- Equipment safety: Electric heaters must be equipped with over-temperature protection (such as bimetallic switches).
Does turbine oil purification solve the problem of free water?
What Is the Ideal ISO Cleanliness Level Achieved by Turbine Oil Purification?
How to Eliminate Water & Varnish in Paper Mill Turbine Oil: The Role of Vacuum Dehydration
Insulation Oil Filtration: Temperature Control Boundaries for Critical Infrastructure
Can Darkened Transformer Oil Be Restored? A Technical Guide to Oil Reclamation