E-mail seo@sino-purification.com
Time:2025-04-24 10:56:41 Reading volume:
Purifying used insulating oil (such as transformer oil, switch oil, etc.) requires a systematic approach to restore its dielectric strength, chemical stability and oxidation resistance to near-new oil standards. The following is a professional and efficient insulating oil regeneration process:
| Pollutants | Source | Hazards |
|------------------|--------------------------|--------------------------------------------------------------------------|
| Moisture | Moisture intrusion, oxidation byproducts | Every 100ppm of moisture ↓ breakdown voltage 30%, accelerated cellulose aging |
| Dissolved gas | Partial discharge, thermal decomposition | Accumulation of flammable gases such as H₂, C₂H₂ causes explosion risk |
| Particles | Equipment wear, fiber shedding | Formation of conductive channels leading to partial discharge (>5μm particles are significantly harmful) |
| Oxidation products | High temperature operation, oxygen contact | When the acid value is >0.1mgKOH/g, the copper winding is corroded and sludge is generated to block the cooling channel |
1. Pretreatment (preliminary purification)
- Mechanical filtration:
- Use a 20μm filter to remove large particles (metal chips, fibers).
- Configure a strong magnetic rod to adsorb ferromagnetic particles (efficiency > 90%).
- Sedimentation separation:
- Stand for 24 hours to allow free water to settle (only suitable for mild pollution with a water content of < 0.1%).
2. Core purification process
(1) Vacuum dehydration and degassing (key step)
- Equipment: two-stage vacuum oil filter (roots pump + rotary vane pump combination)
- Process parameters:
- Vacuum degree: ≤50Pa (absolute pressure)
- Oil temperature: 60-65℃ (avoid >70℃ to accelerate oxidation)
- Atomization method: three-dimensional flash evaporation technology to increase the surface area of the oil film
- Effect:
- Water ≤8ppm (IEC 60814 standard)
- Gas content ≤0.05% (volume ratio)
(2) Precision filtration
- Filter element grade:
- β₅≥200 (corresponding to NAS 1638 level 4)
- Absolute accuracy 1μm (intercept carbon particles, resin precipitates)
- Special design:
- Use a glass fiber filter element (oil-resistant, high temperature resistant)
(3) Adsorption refining (optional)
- Applicable conditions: acid value > 0.05 mgKOH/g or dielectric loss factor tanδ > 0.02 (90°C)
- Method:
- Silica gel/activated alumina: packed adsorption tower treatment (addition amount 3-5% oil weight)
- Molecular sieve: selective adsorption of trace moisture (can be reduced to below 5 ppm)
3. Post-treatment (performance recovery)
- Vacuum standing: The purified oil is left to stand at 50Pa vacuum for 12 hours to remove residual microbubbles.
- Additive supplement:
- Add 0.3% T501 antioxidant (2,6-di-tert-butyl-p-cresol)
- Add 0.1% benzotriazole (metal passivator)
1. Vacuum oil filter:
- Processing capacity ≥1.5 times the oil tank volume/hour (e.g.: 15m³/h equipment for a 10m³ oil tank)
- Equipped with an online moisture monitor (capacitive sensor, accuracy ±1ppm)
2. Adsorption system:
- Dynamic circulation white clay treatment tower (contact time ≥30 minutes)
3. Safety design:
- Explosion-proof heater (surface temperature ≤80℃)
- Oxygen content monitoring (working environment O₂<8%)
1. Temperature control:
- The heating rate in the heating stage is ≤5℃/min to prevent thermal shock from causing oil cracking.
2. Vacuum system maintenance:
- Regularly replace vacuum pump oil (every 200 hours or when the water content is >100ppm).
3. Environmental compliance:
- Waste clay is treated as HW08 hazardous waste, and waste gas is recovered by condensation.
1. Laboratory testing:
- Full analysis: chromatography (DGA), PQ index (particle contamination), rotating oxygen bomb (anti-oxidation).
2. On-site test:
- 72-hour cycle test: monitor breakdown voltage fluctuation <5%.
3. Documentation:
- Generate oil passport (data comparison before and after processing, by IEC 60422).
Through the above process, the insulating oil can be reused 3-5 times (depending on the initial contamination level). For oil used in ultra-high voltage equipment above 500kV, it is recommended to entrust a professional regeneration plant to process it to ensure that the dielectric strength is restored to ≥65kV. In daily maintenance, the oil change cycle can be extended to more than 10 years with the online oil filter device.
Root Causes of Loss of Control in Vacuum Oil Purification Systems
How Industrial Oil Filters Remove Water and Impurities: A Comparison of Technical Principles
How to Choose the Right Industrial Oil Purifier: A Comprehensive Buyer’s Guide
How to Choose the Right Oil Purifier for Different Oil Types?
Double-Stage Vacuum Pumping: The Complete Guide to Transformer Maintenance