Technical specifications and operation points for 110kV transformer insulating oil filtration
1. Oil quality testing:
- Test items: moisture content (≤15ppm), breakdown voltage (≥50kV), dielectric loss factor (90℃≤0.02)
- Sampling specifications: According to the requirements of GB/T 7597, take a 500mL of oil sample for full analysis
2. Equipment selection:
- It is recommended to use a two-stage vacuum oil filter
- Technical parameter requirements:
Vacuum degree ≤5Pa (first-level vacuum chamber)
Heating temperature 60±5℃
Filtration accuracy ≤3μm
3. On-site preparation:
- Build a dustproof shed (humidity ≤60%)
- Prepare enough spare oil (20% of the processing volume)
1. Pretreatment stage:
- Coarse filtration: first remove large particles through a 20μm filter element
- Sedimentation separation: let it stand for 48 hours to discharge free water
2. Main treatment stage:
- Vacuum dehydration:
Temperature of first-level vacuum chamber 50-55℃
Temperature of second-level vacuum chamber 60-65℃
Cycle period ≥5 times
- Precision filtration:
Use a 3μm filter element with β≥200
Pressure difference controlled at 0.15-0.25MPa
3. Post-treatment stage:
- Vacuum oil injection: Keep vacuum degree ≤13Pa
- Standing time: ≥72 hours
| Project | Control standard | Detection frequency |
|--------------|-------------------------|----------|
| Vacuum degree | ≤5Pa (first level) | Real-time monitoring |
| Oil temperature | 60±5℃ | Every hour |
| Water content | ≤10ppm | Every 2 hours |
| Breakdown voltage | ≥60kV | Every 4 hours |
| Gas content | ≤0.5% | Every 8 hours |
1. Safety control:
- Electrostatic grounding resistance of oil pipeline ≤4Ω
- Set combustible gas alarm (alarm value ≤ 10% LEL)
2. Quality assurance measures:
- The amount of oil processed in each batch does not exceed 10 tons
- Establish oil processing curve (water content-time curve)
- The final oil sample is sent to a third party for testing
3. Special treatment:
- For oil products with acid value > 0.05mgKOH/g:
Add white clay adsorption treatment
Extend the cycle time to 8-10 times
1. Electrical performance:
- Breakdown voltage ≥60kV (DL/T 429.9)
- Dielectric loss factor ≤0.005 (90℃)
2. Physical and chemical indicators:
- Water content ≤8ppm
- Gas content ≤0.3%
- Particle size ≤NAS level 8
3. Compatibility test:
- Contact with solid insulating material for 72 hours without abnormality
1. The vacuum degree does not meet the standard:
- Check the oil level of the mechanical pump
- Check the sealing of the vacuum valve
- Check the connection of the bellows
2. Abnormal oil temperature:
- Clean the carbide on the surface of the heater
- Calibrate the PT100 temperature sensor
3. Low filtration efficiency:
- Check the saturation of the filter element
- Adjust the oil pump speed to the rated value
Note: The operation process must strictly follow the requirements of the "Preventive Test Procedures for Power Equipment" (DL/T 596), record key parameters throughout the process, and keep the treated oil sample for reference for 3 months. It is recommended to operate under the guidance of professional technicians, and contact the equipment manufacturer for technical support in complex situations.
Root Causes of Loss of Control in Vacuum Oil Purification Systems
How Industrial Oil Filters Remove Water and Impurities: A Comparison of Technical Principles
How to Choose the Right Industrial Oil Purifier: A Comprehensive Buyer’s Guide
How to Choose the Right Oil Purifier for Different Oil Types?
Double-Stage Vacuum Pumping: The Complete Guide to Transformer Maintenance